Technical Parameters
Parameter Specification
Product Series Eaton 9PX Series
Product Type Double Conversion Online UPS (Rackmount)
Topology Online Double Conversion
Nominal Output Power 6 kVA / 5.4 kW (at 0.9 output power factor)
Input Voltage: 200/208/220/230/240 V AC (Auto-sensing)
Frequency: 50/60 Hz (Auto-sensing)
Connector: Hardwired or specific plug type (check local variant)
Output Voltage: 200/208/220/230/240 V AC (User-selectable)
Frequency: 50/60 Hz ± 1 Hz (Synchronized to bypass)
Output Power Factor: 0.9
Typical Runtime Extended runtime at half load (2.7 kW) due to the "i" configuration. Exact minutes must be verified from the datasheet.
Battery Type: Sealed, maintenance-free Lead-Acid batteries (internal)
Replacement: Hot-swappable, user-replaceable cartridge
Expansion: Supported via external battery packs (e.g., EBM series)
Efficiency >96% in online mode (at full load); >99% in Eaton GreenMode™
Communications Standard: USB, RS-232, Dry Contact
Optional: Slot for Network Management Card (e.g., IPM)
Display & Interface Color Graphical LCD
Form Factor 3U Rackmount (19-inch)
Typical Applications Server Racks, Network Closets, Data Centers, Telecom Installations
Warranty Typically 3 years (including battery)
Standards Compliance IEC 62040-1, CE, cULus, RoHS
Technical Parameters
Parameter Specification
Product Series Eaton 9PX Series
Product Type Double Conversion Online UPS (Tower/Rackmount)
Topology Online Double Conversion
Nominal Output Power 6 kVA / 5.4 kW (at 0.9 output power factor)
Input Voltage: 200/208/220/230/240 V AC (Auto-sensing)
Frequency: 50/60 Hz (Auto-sensing)
Connector: Hardwired or specific plug type (check local variant)
Output Voltage: 200/208/220/230/240 V AC (User-selectable)
Frequency: 50/60 Hz ± 1 Hz (Synchronized to bypass)
Output Power Factor: 0.9
Typical Runtime Extended runtime at half load (2.7 kW) due to the "i" configuration. Exact minutes must be verified from the datasheet as it depends on the specific battery cartridge.
Battery Type: Sealed, maintenance-free Lead-Acid batteries (internal)
Replacement: Hot-swappable, user-replaceable cartridge
Expansion: Supported via external battery packs (e.g., EBM series)
Efficiency >96% in online mode (at full load); >99% in Eaton GreenMode™
Communications Standard: USB, RS-232, Dry Contact
Optional: Slot for Network Management Card (e.g., IPM)
Display & Interface Color Graphical LCD
Form Factor Tower with Integrated Rackmount Kit (RTG)
Typical Applications Server Racks, Network Closets, Data Centers, Medical Equipment
Warranty Typically 3 years (including battery)
Standards Compliance IEC 62040-1, CE, cULus, RoHS
Technical Parameters
Parameter Specification
Product Series Eaton NZM1
Product Type Programmable Electronic Trip Unit (Release) for Air Circuit Breaker
Rated Current (In) of Frame 1300 A (This is the fixed rating for this specific trip unit)
Rated Operational Voltage (Ue) Up to 690 V AC
Rated Insulation Voltage (Ui) 1000 V AC
Rated Frequency 50/60 Hz
Protection Functions L (Long-time Overload), S (Short-time), I (Instantaneous), G (Ground Fault)
Setting Adjustment Programmable via USB connection and dedicated software (e.g., Eaton's NZM Configurator)
Communication Interface USB Port for local configuration and monitoring
Short-Circuit Breaking Capacity (Icu) Dependent on the complete NZM1 breaker assembly, typically very high (e.g., 50kA to 100kA at 400V). Must be verified from the breaker frame's datasheet.
Display Typically includes an LCD or LED display for status and fault indication
Mounting Integrated into a compatible NZM1 circuit breaker frame
Standards Compliance IEC 60947-2, UL 1066, CSA 22.2
Technical Parameters
Parameter Specification
Product Series Eaton NZM1
Product Type Electronic Trip Unit (Release) for Air Circuit Breaker
Rated Current (In) of Frame 4 A (This is the fixed rating for the breaker frame)
Rated Operational Voltage (Ue) Up to 690 V AC
Rated Insulation Voltage (Ui) 1000 V AC
Rated Frequency 50/60 Hz
Protection Functions L (Long-time Overload), S (Short-time), I (Instantaneous), G (Ground Fault)
Ground Fault Protection (Iₙ) Adjustable range (e.g., 0.2 - 0.8 x In or similar, specific to setting)
Short-Circuit Breaking Capacity (Icu) Dependent on the complete breaker assembly, typically high (e.g., 50kA to 100kA at 400V)
Trip Setting Adjustment Via DIP switches and potentiometers on the release unit
Communication Capability No (The "XFIR" version is typically a standard electronic release without communication. Versions with "C" often have communication).
Mounting Integrated into an NZM1 circuit breaker frame
Standards Compliance IEC 60947-2, UL 1066, CSA 22.2
Technical Parameters
Parameter Specification
Product Series Eaton EASY Expansion
Product Type Digital I/O Expansion Module
Compatibility EASY500, EASY600, EASY700 series base units
Number of Digital Inputs 8
Input Voltage 24 V DC (sourced from the base unit via bus connection)
"1" Signal Level ≥ 13 V DC
"0" Signal Level ≤ 5 V DC
Number of Outputs 8
Output Type Electromechanical Relays (Changeover Contacts)
Contact Configuration SPDT (1 Form C) - Each output has one Normally Open (NO) and one Normally Closed (NC) contact.
Rated Load Current per Output 5 A (at 250 V AC, Resistive)
Max. Switching Power per Output AC-15: 1250 VA
DC-13: 90 W (at 24 V DC)
Min. Switching Load 10 mA at 5 V DC
Electrical Life ≥ 100,000 cycles (at rated load)
Mechanical Life ≥ 10,000,000 cycles
Connection Removable screw terminal blocks
Power Supply Via bus connection from the base unit (no external power required)
Mounting DIN Rail (35 mm, EN 60715)
Standards Compliance UL 508, CSA C22.2 No. 14, IEC 61131-2, CE
Technical Parameters
Parameter Specification
Product Series Eaton ESR5
Product Type Miniature General Purpose Relay
Contact Configuration 1 Pole, Normally Open (1NO / SPST-NO)
Coil Voltage 24 V DC
Nominal Power Consumption Approximately 0.9 W
Rated Thermal Current (Ith) 16 A
Rated Operating Voltage (Ue) 250 V AC / 400 V AC (for resistive loads)
Max. Switching Power AC Loads: 3000 VA (at 250V AC)
DC Loads: 90 W (at 24V DC)
Rated Carry Current 20 A
Electrical Life > 100,000 operations (at rated load)
Mechanical Life > 10,000,000 operations
Dielectric Strength Between coil and contacts: 4000 V AC
Connection Type Screw terminal (6.3 x 0.8 mm)
Mounting DIN Rail (with optional adapter), Panel Mount, or PCB Mount
Status Indication Mechanical flag indicator
Standards Compliance IEC/EN 61810-1, UL 508, CSA C22.2 No. 14, cULus
Technical Parameters
Parameter Specification
Product Series Eaton FRCmM
Product Type Residual Current Operated Circuit Breaker (RCBO)
Number of Poles 1 Pole + Neutral (1P+N)
Rated Current (In) 63 A
Rated Voltage 230 V AC
Rated Residual Current (IΔn) 30 mA
RCD Type Type A (Sensitive to AC and pulsating DC residual currents)
Rated Breaking Capacity (Icn) 4.5 kA (4,500 A) according to IEC/EN 60898-1
Tripping Characteristic (MCB) C (Instantaneous trip: 5 to 10 x In) [Note: Common for this series, verify from datasheet]
Mechanical Life ≥ 20,000 cycles
Electrical Life ≥ 10,000 cycles
Terminal Connection Suitable for rigid and flexible copper conductors
Mounting DIN Rail Mounting (35 mm, EN 60715)
Standards Compliance IEC/EN 61009-1, IEC/EN 60898-1
Technical Parameters
Parameter Specification
Product Series Eaton EASY500
Product Type Programmable Relay (Smart Relay)
Power Supply Voltage 100 - 240 V AC, 50/60 Hz
Rated Current from Supply Typically < 50 mA (at 230V AC)
Digital Inputs 12 (The exact number is part of the "512" code. Verify with datasheet)
Input Type Digital, AC or DC version depending on specific model
Input Voltage Typically 24V DC or 110/230V AC (depending on model)
Relay Outputs 8 (The exact number is part of the "512" code. Verify with datasheet)
Output Type Electromechanical Relays (with NO/NC contacts)
Rated Load per Relay Output Typically 5 A / 250 V AC (Resistive)
Program Memory Varies, but sufficient for several hundred network elements
Program Language EASY-SOFT (Ladder Diagram / Function Block style)
Integrated Display Yes, LCD with backlight
Integrated Interface Yes, tactile buttons
Expansion Modules Supported (EASY-...-EXP)
Real-Time Clock Yes (for time-switching functions)
Mounting DIN Rail (EN 60715)
Standards Compliance UL 508, CSA C22.2 No. 14, IEC 61131-2, CE, cULus
Technical Parameters
Parameter Specification
Product Series Eaton XNE (Moeller Series)
Product Type Digital Input Module
Number of Channels 8
Channel Type Digital Input (DI)
Input Type Sinking (compatible with PNP sensors)
Rated Input Voltage 24 V DC
Operating Voltage Range Typically 19.2 - 30 V DC
Input Current per Channel Typically 3-5 mA @ 24V DC
"1" Signal Level ≥ 15 V DC (Logic High)
"0" Signal Level ≤ 5 V DC (Logic Low)
Connection Type Removable screw terminal block
Isolation Between field side and system side
Status Indication LED per channel (green)
Mounting DIN Rail (35 mm, EN 60715)
Compatibility Eaton XNE PLC Systems (e.g., with XNExx CPU or BUS Coupler)
Standards Compliance IEC 61131-2, UL 508, CE, cULus