Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, ZB Series
Model Number ZB32C-24
Output Voltage 24V DC
Rated Output Power 32 W
Rated Output Current 1.3 A
Input Voltage Range 85-264V AC (Wide range, auto-sensing)
Input Frequency Range 47-63 Hz
Efficiency Typically >85%
Power Factor (PF) Typically >0.9
Output Adjustment Range Typically ±10% (e.g., 21.6-26.4V DC)
Mounting DIN Rail (35mm)
Protection Overload Protection, Overvoltage Protection, Short-Circuit Protection
Standards Compliance IEC/EN 61347-1, IEC/EN 61347-2-13, UL 1310, CSA C22.2 No. 223
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, PL9 Series
Model Number PL9-C32/2
Fuse Standard & Rating IEC gG (General Application)
Rated Current: 32 A
Number of Poles / Quantity 2 pieces (2-pole set)
Rated Voltage 500V AC
Breaking Capacity 50 kA (50,000 A) at 500V AC
Standards Compliance IEC 60269-1, IEC 60269-2-1
Fuse Dimension 10 x 38 mm (Diameter x Length)
Mounting Requires compatible fuse holder for 10x38mm fuses
Utilization Category gG - Full-range breaking capacity for general applications
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, ZB Series
Model Number ZB12C-10
Output Voltage 12V DC
Rated Output Power 10 W
Rated Output Current 0.83 A
Input Voltage Range 85-264V AC (Wide range, auto-sensing)
Input Frequency Range 47-63 Hz
Efficiency Typically >80%
Power Factor (PF) Typically >0.9
Output Adjustment Range Typically ±10% (e.g., 10.8-13.2V DC)
Mounting DIN Rail (35mm)
Protection Overload Protection, Overvoltage Protection, Short-Circuit Protection
Standards Compliance IEC/EN 61347-1, IEC/EN 61347-2-13, UL 1310, CSA C22.2 No. 223
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, PKZM4 Series
Model Number PKZM4-58
Rated Operational Current (Ie) 58 A
Rated Current Setting (Ir) Adjustable, typically up to 58A
Poles 3-Pole
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 690V AC
Utilization Category AC-3 (Squirrel cage motor: Starting, switching off during running)
Motor Power Rating (at 400V AC) 30 kW / 40 HP (Approximate)
Short-Circuit Breaking Capacity (Icu) Typically 50 kA at 400V AC (Confirm with specific datasheet)
Trip Class Class 10 (Standard for motor protection)
Standards Compliance IEC/EN 60947-2, IEC/EN 60947-4-1
Mounting DIN Rail (35mm)
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, ZB Series
Model Number ZB12C-1,6
Output Voltage 12V DC
Rated Output Power 1.6 W
Rated Output Current 0.13 A
Input Voltage Range 85-264V AC (Wide range, auto-sensing)
Input Frequency Range 47-63 Hz
Efficiency Typically >70%
Mounting DIN Rail (35mm)
Protection Overload Protection, Short-Circuit Protection
Standards Compliance IEC/EN 61347-1, IEC/EN 61347-2-13
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILRC Series
Model Number DILRC-22
Rated Operational Current (Ie) 22 A (for AC-1 category, resistive loads)
Poles 4-Pole (Typically 4 Normally Open (NO) contacts)
Rated Operational Voltage (Ue) Up to 690V AC
Control Coil Voltage Available in multiple standard AC and DC voltages (e.g., 24V AC/DC, 110V AC, 230V AC, etc.). The specific voltage is not defined by "22" and must be specified when ordering.
Utilization Categories AC-1: Non-inductive or slightly inductive loads
AC-15: Control of electromagnetic loads (≤ 720 VA)
DC-1: Non-inductive or slightly inductive loads
DC-13: Control of electromagnetic loads
Mechanical Life ~ 10 - 30 million operations (typical for this series)
Electrical Life Varies by utilization category (e.g., ~ 1-3 million operations at rated AC-15 load)
Mounting Standard 35mm DIN Rail (EN 60715)
Standards Compliance IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14
Terminal Type Cage Clamp or Screw Clamp
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, NZM Series
Model Number NZMB1-4-A125
Rated Current 125 A (Frame Size)
Poles 4-Pole
Rated Operational Voltage (Ue) Up to 690V AC
Rated Insulation Voltage (Ui) 800V AC
Trip Unit Type Type A - Adjustable Electronic Trip Unit
Protection Functions L - Long-time Delay (Overload)
S - Short-time Delay (Short-Circuit)
I - Instantaneous (Short-Circuit)
Breaking Capacity (Icu) High interrupting capacity (e.g., 25kA, 35kA, or higher depending on specific rating and voltage)
Standards Compliance IEC 60947-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, NZM Series
Model Number NZMN1-A63
Rated Current 63 A (Frame Size)
Poles Typically 3-Pole (Pole configuration may vary, confirm with specific order code)
Rated Operational Voltage (Ue) Up to 690V AC
Rated Insulation Voltage (Ui) 800V AC
Trip Unit Type Type A - Adjustable Electronic Trip Unit
Protection Functions L - Long-time Delay (Overload)
S - Short-time Delay (Short-Circuit)
I - Instantaneous (Short-Circuit)
Breaking Capacity (Icu) High interrupting capacity (Typically 25 kA to 50 kA depending on specific voltage rating)
Standards Compliance IEC 60947-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, M22 Series
Model Number M22-PVT
Sensor Type Inductive Proximity Sensor
Housing Material Typically Nickel-plated brass or Stainless Steel
Thread Size M22 x 1.5
Connection Type PVC Cable (Specific length and conductor count vary - e.g., 2m 3-core)
Sensing Distance 5 mm (Standard for M22 inductive sensors)
Output Type DC 3-wire (Typically PNP or NPN, selectable or fixed - check datasheet)
Supply Voltage 10-30V DC
Rated Operating Current Typically ≤ 200 mA
Switching Frequency Typically ≤ 500 Hz
Protection Degree IP67
Standards Compliance IEC 60947-5-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILM Series
Model Number DILM9-10
Rated Operational Current (Ie) 9 A at AC-3, 400V
Thermal Current (Ith) 9 A
Poles (Main Circuit) 3 (Normally Open)
Auxiliary Contacts 1 NO (Normally Open) + 1 NC (Normally Closed) - Convertible
Rated Operational Voltage (Ue) Up to 690V AC
Control Coil Voltage Available in multiple standard AC voltages (e.g., 24V, 110V, 230V, 400V AC). The specific voltage must be specified when ordering.
Utilization Categories AC-3: Squirrel cage motors: Starting, switching off during running
AC-1: Non-inductive or slightly inductive loads
Motor Rating (at 400V AC) 4 kW / 5.5 HP
Mechanical Life ~ 15 million operations
Electrical Life (AC-3) ~ 1.5 million operations
Mounting Standard 35mm DIN Rail (EN 60715) or screw mounting
Standards Compliance IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 14
Terminal Type Cage Clamp / Screw Clamp