Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, PKZM0 Series
Model Number PKZM0-6.3
Rated Operational Current (Ie) 6.3 A
Poles 3-Pole
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 750V AC
Utilization Category AC-3 (Squirrel cage motor: Starting, switching off during running)
Motor Power Rating (at 400V AC) ~2.2 kW / 3 HP (Approximate)
Short-Circuit Breaking Capacity (Icu) Typically 6 kA or higher at 400V AC (Confirm with datasheet)
Trip Class Class 10
Operation Type Manual (Toggle Handle)
Mounting DIN Rail (35mm)
Standards Compliance IEC/EN 60947-4-1
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, PKZM0 Series
Model Number PKZM0-32
Rated Operational Current (Ie) 32 A
Poles 3-Pole
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 750V AC
Utilization Category AC-3 (Squirrel cage motor: Starting, switching off during running)
Motor Power Rating (at 400V AC) ~15 kW / 20 HP (Approximate)
Short-Circuit Breaking Capacity (Icu) Typically 6 kA or higher at 400V AC (Confirm with datasheet)
Trip Class Class 10
Operation Type Manual (Toggle Handle)
Mounting DIN Rail (35mm)
Standards Compliance IEC/EN 60947-4-1
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, MFD Series
Model Number MFD-CP8-NT
Power Supply Voltage 24V DC (Typical for "C" variant)
Output Relay DPDT (2 CO) - 2 Changeover contacts
Contact Rating: Typically 8A @ 250V AC
Timing Ranges Multiple ranges selectable (e.g., from 0.1 seconds up to 100 hours)
Functions Multiple timing functions selectable (e.g., On-delay, Off-delay, Interval, Flasher, etc.)
Accuracy ±0.5% of set time ± 20 ms
Mounting DIN Rail (35mm)
Display / Indication Digital Display and LED Status Indicators
Standards Compliance IEC/EN 61812-1, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, T3 Series
Model Number T3-4-15682/I2/SVB
Rated Operational Current (Ie) 63 A (at AC-23)
Number of Poles 4-Pole (3 phases + neutral)
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 750V AC
Rated Impulse Withstand Voltage (Uimp) 8 kV
Utilization Categories AC-22 (Switching mixed resistive and inductive loads)
AC-23 (Switching motor loads)
Breaking Capacity Typically 30 kA (at 400V AC)
Auxiliary Contacts I2 - Specific auxiliary contact configuration (e.g., 1 NO + 1 NC)
Terminal Type SVB - Shrouded Terminal Barrier for enhanced safety
Operation Type Rotary Handle Operation
Mechanical Life ~ 20,000 operations
Electrical Life ~ 5,000 operations (at rated current)
Mounting DIN Rail (35mm)
Standards Compliance IEC/EN 60947-3
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, T0 Series
Model Number T0-3-15680/11/SVB
Rated Operational Current (Ie) 63 A (at AC-23)
Number of Poles 3-Pole
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 750V AC
Rated Impulse Withstand Voltage (Uimp) 8 kV
Utilization Categories AC-22 (Switching mixed resistive and inductive loads)
AC-23 (Switching motor loads)
Breaking Capacity Typically 30 kA (at 400V AC)
Auxiliary Contacts 11 - Specific auxiliary contact configuration (e.g., 1 NO contact)
Terminal Type SVB - Shrouded Terminal Barrier for enhanced safety
Operation Type Rotary Handle Operation
Mechanical Life ~ 20,000 operations
Electrical Life ~ 5,000 operations (at rated current)
Mounting DIN Rail (35mm)
Standards Compliance IEC/EN 60947-3
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, P3 Series
Model Number P3-63/EA/SVB/NL
Rated Current (In) 63 A
Number of Poles 3-Pole
Rated Operational Voltage (Ue) 400/415V AC (Three-Phase)
Rated Insulation Voltage (Ui) 500V AC
Breaking Capacity (Icn) Typically 10 kA (Please confirm with specific catalog)
Tripping Characteristic Type C (Instantaneous trip: 5-10 x In)
Auxiliary Function EA - Alarm Switch (Signals trip condition via a separate contact)
Terminal Type SVB - Shrouded Terminal Barrier (Finger Protection)
Variant NL - Specific variant or regional designation (e.g., for Netherlands market or specific certification)
Mounting Standard 35mm DIN Rail (EN 60715)
Standards Compliance IEC/EN 60898-1
Technical Parameters
Category Parameter Specification
Input Characteristics Input Voltage 100 - 240 VAC (Wide Range, Auto-Sensing)
Input Frequency 50 / 60 Hz
Input Current Max. 0.7 A @ 100 VAC
Inrush Current Limiting Yes (NTC Thermistor)
Output Characteristics Output Voltage 12 V DC
Voltage Adjustment Range ~11 - 13.2 V DC (via potentiometer)
Rated Output Current 2.1 A
Rated Output Power 25 W
Efficiency Typically > 80%
Ripple and Noise < 150 mVpp (typical)
Line Regulation < 1.0%
Load Regulation < 1.0%
Protection & Safety Overload Protection Electronic, auto-recovery (105% - 150% of Iout)
Overvoltage Protection Electronic, auto-recovery
Standards CE Marked
Environmental & Mechanical Operating Temperature -25 °C to +70 °C (with derating above 50-60°C)
Storage Temperature -40 °C to +85 °C
Cooling Method Fanless (Convection)
Mounting Standard 35 mm DIN Rail
Enclosure Protection IP20 (Terminal Protection)
Connections Screw Terminals
Category Parameter Specification
Input Characteristics Input Voltage 100 - 240 VAC (Wide Range)
Input Frequency 50 / 60 Hz
Input Current Max. 0.9 A @ 100 VAC
Inrush Current Limiting Yes (NTC Thermistor)
Output Characteristics Output Voltage 12 V DC
Voltage Adjustment Range ~11 - 13.2 V DC (via potentiometer)
Rated Output Current 2.7 A
Rated Output Power 32 W
Efficiency Typically > 81%
Ripple and Noise < 150 mVpp
Line Regulation < 1.0%
Load Regulation < 1.0%
Protection & Safety Overload Protection Electronic, auto-recovery (105% - 150% of Iout)
Overvoltage Protection Electronic, auto-recovery
Standards CE, cULus Listed (Typically)
Environmental & Mechanical Operating Temperature -25 °C to +70 °C (with derating above 60°C)
Storage Temperature -40 °C to +85 °C
Cooling Method Fanless (Convection)
Mounting Standard 35 mm DIN Rail
Enclosure Protection IP20
Connections Screw Terminals
Safety Class Class I (Protective Earth connection required)
Category Parameter Specification
Input Characteristics Input Voltage 100 - 240 VAC (Wide Range)
Input Frequency 50 / 60 Hz
Input Current Max. 0.9 A @ 100 VAC
Inrush Current Limiting Yes (NTC Thermistor)
Output Characteristics Output Voltage 24 V DC (Note: P1-32/E typically refers to the 24V model)
Voltage Adjustment Range ~22 - 26.4 V DC (via potentiometer)
Rated Output Current 1.3 A (for 24V model)
Rated Output Power 32 W
Efficiency Typically > 81%
Ripple and Noise < 150 mVpp
Redundancy & Monitoring Redundancy Function Integrated OR-ing diode for parallel operation
Signal Contact DC-OK relay contact (floating, 24V DC / 1A max.) for monitoring output status
Protection & Safety Overload Protection Electronic, auto-recovery (105% - 150% of Iout)
Overvoltage Protection Electronic, auto-recovery
Standards CE, cULus Listed
Environmental & Mechanical Operating Temperature -25 °C to +70 °C (with derating above 60°C)
Storage Temperature -40 °C to +85 °C
Cooling Method Fanless (Convection)
Mounting Standard 35 mm DIN Rail
Enclosure Protection IP20
Connections Screw Terminals
Category Parameter Specification
Display Screen Size 4-inch TFT LCD
Resolution 480 x 272 pixels
Color Depth 65K colors
Touch Screen Resistive
Hardware & Performance Processor ARM-based
Memory (User) Typically 8 MB for projects, recipes, data logs
Integrated I/O Digital Inputs: 4 x 24V DC
Digital Outputs: 4 x 24V DC, 0.5A (PNP)
Analog Input: 1 x 0-10V / 0-20mA
Integrated Safety Safety Inputs: 2 x (for e.g., emergency stop, safety gates)
Safety Outputs: 2 x (for e.g., safe torque off) - Compliant with SIL 2 / PL c
Communication Interfaces Ethernet Port 1 x 10/100 Mbit/s (for programming, HMI communication, and PLC networking)
Fieldbus PROFINET and/or EtherNet/IP (configurable as controller or device)
Serial Port 1 x RS-485/422
USB Port 1 x USB 2.0 Host (for connecting keyboard, mouse, or for data transfer)
Software Integrated PLC Runtime Eaton's SPC (Smart Process Controller) or SPS (Smart Programmable Controller)
Programming Software Eaton XVS software package (for HMI design, standard and safety logic programming)
Included License Pre-installed runtime license for the integrated PLC and HMI (SW suffix indicates this)
Electrical Supply Voltage 24 V DC (typical range: 19.2 - 28.8 V DC)
Power Consumption Typically 15-20 W
Environmental & Mechanical Protection Rating Front: IP65 (dust-tight and protected against water jets)
Rear: IP20
Mounting Panel Mount (Cut-out dimensions required)
Operating Temperature 0 °C to +55 °C