PKZMO-1.6
Technical Specification
Parameter Specification / Typical Value
Manufacturer / Brand Eaton
Model Number PKZMO-1.6
Product Line PKZ (Moeller Series)
Rated Operational Current for Motors (Ie) 1.6 A
Setting Range for Thermal Overload Approx. 1.0 - 1.6 A (adjustable)
Poles (Main Circuit) 3
Rated Operational Voltage (Ue) 690 V AC
Rated Insulation Voltage (Ui) 690 V / 750 V AC
Rated Ultimate Breaking Capacity (Icu/@400V) e.g., 50 kA or 100 kA (Must be verified from datasheet)
Tripping Class Class 10 (Standard for general motors, trips within 10 seconds at 7.2 x Ir)
Short-Circuit Protection Setting Fixed, based on the device design (e.g., 12 x Ie or higher)
Auxiliary Contacts Can typically be fitted with one or more auxiliary contact modules (e.g., PKZM0-1X) to signal the trip status.
Mounting DIN Rail Mount (35mm)
Standards Compliance IEC/EN 60947-2, IEC/EN 60947-4-1