PLD9-32/1N/C/003
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series PLD9
Product Model PLD9-32/1N/C/003
Product Type Type 2 / Class II Surge Protective Device (SPD)
Rated Voltage (Uc) 230/400 V AC
Nominal System Voltage 230 V AC (Single-Phase + N)
Protection Mode 1-Pole + Neutral (1P+N)
(L-PE, N-PE)
Max. Discharge Current (Imax - 8/20 µs) 32 kA per mode
Nominal Discharge Current (In - 8/20 µs) 15 kA
Voltage Protection Level (Up) ≤ 1.5 kV
Response Time < 25 ns
Backup Overcurrent Protection (Recommended) 25 A gG/gL (or per local regulations)
Status Indication Visual Indicator (Green: OK; Red: End-of-Life)
Remote Signalling Contact 1 Changeover Contact (SPDT)
Mounting 35 mm DIN Rail (EN 60715)
Connection Screw Terminal
Approvals / Certifications CE, IEC 61643-11