Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, PKZM0 Series
Model Number PKZM0-20
Rated Operational Current (Ie) 20 A
Rated Current Setting (Ir) Adjustable, typically from 0.1A to 20A (or a specific range within this)
Poles 3-Pole
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 690V AC
Utilization Category AC-3 (Squirrel cage motor: Starting, switching off during running)
Motor Power Rating (at 400V AC) 9 kW / 12 HP (Approximate)
Short-Circuit Breaking Capacity (Icu) Typically 50 kA at 400V AC (Confirm with specific datasheet)
Trip Class Class 10 (Standard for motor protection)
Standards Compliance IEC/EN 60947-2, IEC/EN 60947-4-1
Mounting DIN Rail (35mm)
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, SL7 Series
Model Number SL7-100-L-RYG-24LED
Mounting Diameter 30 mm (Cut-out: Ø30.5 mm)
Function Illuminated Pushbutton / Indicator Light
Lens Type Multi-lens (RYG) - Red, Yellow, Green
Operating Voltage 24V DC
Light Source LED (Long-life, low power consumption)
Contact Block 1 NO (Normally Open) pushbutton contact (Typically)
Protection Degree IP65 (Front panel, when properly mounted)
Mounting Panel Mount from the front with integrated snap-in mechanism
Standards Compliance IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, LZM2 Series
Model Number LZM2-A160
Rated Current 160 A (Frame Size)
Poles 3-Pole
Rated Operational Voltage (Ue) Up to 690V AC
Rated Insulation Voltage (Ui) 800V AC
Trip Unit Type Type A - Adjustable Electronic Trip Unit
Protection Functions L - Long-time Delay (Overload)
S - Short-time Delay (Short-Circuit)
I - Instantaneous (Short-Circuit)
Breaking Capacity (Icu) High interrupting capacity (e.g., 35kA, 50kA, or 65kA depending on specific rating and voltage - confirm with datasheet)
Standards Compliance IEC 60947-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, NZM Series
Model Number NZM1-XTVD-0
Compatibility NZM1 series Molded Case Circuit Breakers
Function Universal Draw-Out Mechanism Kit
Mounting Installs into a compatible switchboard/panel
Position Indication Typically includes indicators for CONNECTED, TEST, DISCONNECTED positions
Standards Compliance Designed to comply with the same standards as the NZM1 breaker (IEC 60947-2)
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, EMT6 Series
Model Number EMT6-DB
Power Supply Voltage 24-240V AC/DC (Wide range, auto-sensing)
Output Relay DPDT (2 CO) - 2 Changeover contacts
Contact Rating: Typically 8A @ 250V AC
Timing Ranges Multiple ranges selectable (e.g., from 0.05 seconds up to 100 hours)
Functions Multiple timing functions selectable (e.g., On-delay, Off-delay, Interval, Flasher, etc.)
Accuracy ±0.5% of set time ± 20 ms (typical for digital timers)
Mounting DIN Rail (35mm)
Display / Indication LED Status Indicators (Power, Output state)
Standards Compliance IEC/EN 61812-1, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, ZB Series
Model Number ZB32C-24
Output Voltage 24V DC
Rated Output Power 32 W
Rated Output Current 1.3 A
Input Voltage Range 85-264V AC (Wide range, auto-sensing)
Input Frequency Range 47-63 Hz
Efficiency Typically >85%
Power Factor (PF) Typically >0.9
Output Adjustment Range Typically ±10% (e.g., 21.6-26.4V DC)
Mounting DIN Rail (35mm)
Protection Overload Protection, Overvoltage Protection, Short-Circuit Protection
Standards Compliance IEC/EN 61347-1, IEC/EN 61347-2-13, UL 1310, CSA C22.2 No. 223
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, PL9 Series
Model Number PL9-C32/2
Fuse Standard & Rating IEC gG (General Application)
Rated Current: 32 A
Number of Poles / Quantity 2 pieces (2-pole set)
Rated Voltage 500V AC
Breaking Capacity 50 kA (50,000 A) at 500V AC
Standards Compliance IEC 60269-1, IEC 60269-2-1
Fuse Dimension 10 x 38 mm (Diameter x Length)
Mounting Requires compatible fuse holder for 10x38mm fuses
Utilization Category gG - Full-range breaking capacity for general applications
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, ZB Series
Model Number ZB12C-10
Output Voltage 12V DC
Rated Output Power 10 W
Rated Output Current 0.83 A
Input Voltage Range 85-264V AC (Wide range, auto-sensing)
Input Frequency Range 47-63 Hz
Efficiency Typically >80%
Power Factor (PF) Typically >0.9
Output Adjustment Range Typically ±10% (e.g., 10.8-13.2V DC)
Mounting DIN Rail (35mm)
Protection Overload Protection, Overvoltage Protection, Short-Circuit Protection
Standards Compliance IEC/EN 61347-1, IEC/EN 61347-2-13, UL 1310, CSA C22.2 No. 223
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, PKZM4 Series
Model Number PKZM4-58
Rated Operational Current (Ie) 58 A
Rated Current Setting (Ir) Adjustable, typically up to 58A
Poles 3-Pole
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 690V AC
Utilization Category AC-3 (Squirrel cage motor: Starting, switching off during running)
Motor Power Rating (at 400V AC) 30 kW / 40 HP (Approximate)
Short-Circuit Breaking Capacity (Icu) Typically 50 kA at 400V AC (Confirm with specific datasheet)
Trip Class Class 10 (Standard for motor protection)
Standards Compliance IEC/EN 60947-2, IEC/EN 60947-4-1
Mounting DIN Rail (35mm)
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, ZB Series
Model Number ZB12C-1,6
Output Voltage 12V DC
Rated Output Power 1.6 W
Rated Output Current 0.13 A
Input Voltage Range 85-264V AC (Wide range, auto-sensing)
Input Frequency Range 47-63 Hz
Efficiency Typically >70%
Mounting DIN Rail (35mm)
Protection Overload Protection, Short-Circuit Protection
Standards Compliance IEC/EN 61347-1, IEC/EN 61347-2-13