Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM
Product Model IZM65N3-A10WH
Product Type Fixed Mounted Air Circuit Breaker (ACB)
Number of Poles 3 Poles
Rated Operational Voltage (Ue) 690 V AC
Frame Size (Inm) 630 A
Rated Current (In) 630 A (Fixed)
Rated Ultimate Breaking Capacity (Icu) at 415V 50 kA (IEC 60947-2)
Trip Unit Type Fixed Thermal-Magnetic (Non-adjustable)
Protection Functions Overload (Thermal), Short-Circuit (Magnetic)
Mounting Fixed Installation in Switchboard
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM97
Product Model IZM97B4C-V25W
Product Type Fixed Mounted Air Circuit Breaker (ACB)
Number of Poles 4 Poles (3 Poles + Neutral)
Rated Insulation Voltage (Ui) 1000 V AC
Rated Operational Voltage (Ue) 690 V AC
Frame Size (Inm) 3200 A
Rated Current (Iu) 3200 A (Adjustable via trip unit)
Rated Ultimate Breaking Capacity (Icu) at 415V 150 kA (IEC 60947-2)
Trip Unit V25W (Advanced Electronic Trip Unit)
Protection Functions Long-time, Short-time, Instantaneous, Ground Fault
Measurement & Monitoring Current, Voltage, Power, Energy, Power Factor, Frequency, Harmonics (THD)
Communication Protocols Embedded Ethernet (Modbus TCP), RS-485 (Modbus RTU)
Display Graphical LCD Display
Mounting Fixed Installation in Switchboard
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM91
Product Model IZM91H3-V08CW
Product Type Draw-Out Air Circuit Breaker (ACB)
Number of Poles 3 Poles
Rated Operational Voltage (Ue) 690 V AC
Frame Size (Inm) 800 A
Rated Current (Iu) 800 A (Adjustable via trip unit)
Rated Ultimate Breaking Capacity (Icu) at 415V 65 kA (IEC 60947-2)
Trip Unit V08CW (Electronic Trip Unit with integrated Comm & Metering module)
Protection Functions Long-time, Short-time, Instantaneous, Ground Fault
Measurement Functions Current, Voltage, Power, Energy, Power Factor, Frequency, etc.
Communication Protocols Integrated Modbus RTU (RS-485)
Mounting Style Draw-Out
Display LCD Display
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series NWI
Product Model NWI616
Product Type Insulation Monitoring Device (IMD)
Application IT (Ungrounded) Systems (AC/DC)
Rated System Voltage (Un) 0...797 V AC / 0...1100 V DC
Measuring Voltage < 50 V (Safe measuring voltage for the system)
Insulation Resistance Measuring Range 1...1999 kΩ
Response Value (R) Adjustable, 10...1000 kΩ
Response Delay Time (t) Adjustable, 0...30 s
Outputs 2 Changeover Relay Contacts (for Pre-alarm & Main Alarm)
Display Digital LCD Display
Auxiliary Power Supply (Us) 24...230 V AC/DC (Wide Range)
Fault Location Supports connection of external current transformers for fault location systems
Mounting DIN Rail Mounting (35 mm)
Standards IEC 61557-8
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series NZM
Product Model NZM3-XAVS
Product Type Undervoltage Release (UVR)
Compatibility Designed for NZM Series Circuit Breakers (Specific frame sizes must be verified)
Rated Control Supply Voltage (Us) 24...240 V AC/DC (Wide Range)
Trip Delay on Power Loss Typically instantaneous (within 100-500 ms)
Function Trips the circuit breaker when the supply voltage drops below a preset level. The breaker cannot be reclosed until the supply voltage is restored to a sufficient level.
Mounting Side-mounted onto compatible NZM circuit breakers
Connection Screw terminals for control wiring
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series NZM
Product Model NZMN3-A400-E
Product Type Miniature Circuit Breaker (MCB) with Auxiliary Contact
Standards IEC 60947-2
Number of Poles 3 Poles (3P)
Rated Current (Iₙ) 40 A
Tripping Characteristic / Curve Type C (Instantaneous trip: 5 to 10 x Iₙ)
Rated Operational Voltage (Uₑ) 400 V AC, 50/60 Hz
Rated Insulation Voltage (Uᵢ) 500 V AC
Breaking Capacity (Icu) 10 kA at 400V AC
Auxiliary Contact 1 NO (Normally Open) - [Note: The "E" suffix typically signifies an auxiliary contact, but the exact configuration (NO/NC) should be verified with the official datasheet. Some coding systems use "E" for NO contact.]
Electrical Life 10,000 cycles
Mechanical Life 20,000 cycles
Mounting 35 mm DIN Rail (EN 60715)
Terminal Capacity Up to 25 mm²
Approvals / Certifications CE, CCC, IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM97
Product Model IZM97B3-U20W
Product Type Fixed Mounted Air Circuit Breaker (ACB)
Number of Poles 3 Poles
Rated Insulation Voltage (Ui) 1000 V AC
Rated Operational Voltage (Ue) 690 V AC
Frame Size (Inm) 3200 A
Rated Current (Iu) 3200 A (Adjustable via trip unit)
Rated Ultimate Breaking Capacity (Icu) at 415V 150 kA (IEC 60947-2)
Trip Unit U20W (Advanced Electronic Trip Unit)
Protection Functions Long-time, Short-time, Instantaneous, Ground Fault, Load Monitoring
Measurement & Monitoring Current, Voltage, Power, Energy, Power Factor, Frequency, Harmonics (THD)
Communication Protocols Embedded Ethernet (Modbus TCP), RS-485 (Modbus RTU)
Display Graphical LCD Display
Mounting Fixed Installation in Switchboard
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Designation IZM-DTP+EPA (Combination Kit)
Compatible Series Eaton IZM Series Air Circuit Breakers
Components Included 1 x Digital Test Plug (IZM-DTP)
1 x Extended Protection Adapter (IZM-EPA)
Digital Test Plug (DTP) Function Secondary Injection Testing of the Electronic Trip Unit
Extended Protection Adapter (EPA) Function Provides connection points for external Earth Fault (Ground Fault) protection sensors.
Typical Use Case • Testing & Commissioning: Verify trip unit settings and functionality.
• Enhanced Protection: Implement comprehensive ground fault protection by connecting external CBCTs (Core Balance Current Transformers).
Connection Plugs directly into the electronic trip unit of compatible IZM breakers.
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM97
Product Model IZM97N3-V25F
Product Type Fixed Mounted Air Circuit Breaker (ACB)
Number of Poles 3 Poles
Rated Insulation Voltage (Ui) 1000 V AC
Rated Operational Voltage (Ue) 690 V AC
Frame Size (Inm) 2500 A
Rated Current (Iu) 2500 A (adjustable via trip unit)
Rated Ultimate Breaking Capacity (Icu) at 415V 100 kA (IEC 60947-2)
Trip Unit V25F (Electronic Trip Unit)
Protection Functions Long-time, Short-time, Instantaneous, Ground Fault
Measurement Functions Current, Voltage (with external VT), Power, Energy, etc.
Communication Supports communication modules (optional)
Display LCD Display
Mounting Fixed Installation in Switchboard
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZMX
Product Model IZMX16H3-V12W
Product Type Molded Case Circuit Breaker (MCCB)
Number of Poles 3 Poles
Rated Operational Voltage (Ue) 400 V AC (50/60 Hz)
Frame Size (Iu) 160 A
Rated Current (In) Adjustable, up to 160 A
Rated Ultimate Breaking Capacity (Icu) at 415V 36 kA (IEC 60947-2)
Trip Unit Type V12W Electronic Trip Unit
Protection Functions Long-time delay (L), Short-time delay (S), Instantaneous (I), Ground-fault (G)
Measurement Functions Current, Voltage, Power, Energy, Power Factor, Frequency
Communication Supports optional communication modules (e.g., for Modbus)
Display LCD display for parameter setting and measurement reading
Mounting Fixed Installation
Standards IEC 60947-2