Category Parameter Specification
Application Protected Circuit Analog signals (e.g., 4-20 mA)
Connection In-series with the signal line
Electrical Characteristics Nominal Voltage 8 V DC
Max. Operating Voltage 12 V DC
Nominal Current ≤ 250 mA
Voltage Drop Typically < 1 V
Surge Protection Performance Test Waveform (IEC 61643-21) 1.2/50 μs (Voltage) - 8/20 μs (Current)
Nominal Discharge Current (In) 5 kA (8/20 μs)
Max. Discharge Current (Imax) 10 kA (8/20 μs)
Protection Level (Up) < 25 V (at In = 5 kA, 8/20 μs)
General Data Number of Channels 1
Connection Type Screw terminals
Mounting 35 mm DIN Rail
Housing Material Plastic (PA 6.6)
Operating Temperature -40 °C to +80 °C
Standards / Approvals IEC 61643-21, CE
Category Parameter Specification
Application Protected Circuit 2-wire Analog signals (e.g., 4-20 mA loops)
Connection In-series with the signal line
Electrical Characteristics Nominal Voltage 8 V DC
Max. Continuous Operating Voltage Uc 12 V DC
Nominal Current ≤ 250 mA
Voltage Drop Typically < 1 V
Insertion Loss Typically negligible
Surge Protection Performance Test Waveform (IEC 61643-21) 1.2/50 μs (Voltage) - 8/20 μs (Current)
Nominal Discharge Current (In) 5 kA (8/20 μs)
Max. Discharge Current (Imax) 10 kA (8/20 μs)
Protection Level (Up) < 25 V (at In = 5 kA, 8/20 μs)
General Data Number of Poles / Channels 2 (for series connection in one signal loop)
Connection Type Screw terminals
Mounting 35 mm DIN Rail
Housing Material Plastic
Operating Temperature -40 °C to +80 °C
Standards / Approvals IEC 61643-21, CE
Category Parameter Specification / Typical Value
Application & Configuration Protected Circuit Signal circuits (e.g., 4-20 mA, digital I/O)
Circuit Configuration 2-pole (Line-to-Line and Line-to-Ground protection)
Connection In-series with the signal line
Electrical Characteristics Nominal Voltage 8 - 24 V DC (Typical for signal applications)
Max. Continuous Operating Voltage (Uc) ~30 V DC (Please verify in datasheet)
Nominal Current (In) Up to 250 mA (Suitable for most signal loops)
Voltage Drop < 1.5 V (Low, to minimize impact on the signal)
Surge Protection Performance Standards Complies with IEC 61643-21
Nominal Discharge Current (In) 5 kA (8/20 μs waveform)
Max. Discharge Current (Imax) 10 kA (8/20 μs waveform)
Protection Level (Up) < 40 V (at In, typical for this class)
General Data Mounting 35 mm DIN Rail
Connection Type Screw terminals
Housing Material Plastic (PA 6.6)
Operating Temperature -40 °C to +80 °C
Status Indication None (This is a basic model without visual fault indicator)
Category Parameter Specification / Typical Value
Input Characteristics Input Voltage 100 - 240 VAC (Wide Range, Auto-Sensing)
Input Frequency 50 / 60 Hz
Input Current Max. ~1.5 A @ 100 VAC
Inrush Current Limiting Yes
Output Characteristics Output Voltage Approx. 14 V DC (Critical: Must verify with datasheet)
Rated Output Current ~4.5 A (Calculated from 63W / 14V)
Rated Output Power 63 W
Efficiency Typically > 89% (High efficiency characteristic of P3 series)
Ripple and Noise Typically < 100 mVpp
Line Regulation < 0.5%
Load Regulation < 0.5%
Monitoring & Signaling Signal Contact (H11) DC-OK Relay (Floating changeover contact)
Contact Rating Typically 24V DC / 2A (or 230V AC / 2A)
Function Closes when output voltage is normal; opens on failure.
Protection & Safety Overload Protection Electronic, auto-recovery
Overvoltage Protection Electronic, auto-recovery
Short-Circuit Protection Yes, electronic with auto-recovery
Standards CE, cULus Listed, GL (Marine)
Environmental & Mechanical Operating Temperature -25 °C to +70 °C (with derating above 60°C)
Cooling Method Fanless (Convection)
Mounting Standard 35 mm DIN Rail
Protection Rating IP20
Connections Screw Terminals
Category Parameter Specification
Application Protected Circuit 2-wire Analog signals (e.g., 4-20 mA loops)
Connection In-series with the signal line
Electrical Characteristics Nominal Voltage 8 V DC
Max. Continuous Operating Voltage Uc 12 V DC
Nominal Current ≤ 250 mA
Voltage Drop Typically < 1 V
Insertion Loss Typically negligible
Surge Protection Performance Test Waveform (IEC 61643-21) 1.2/50 μs (Voltage) - 8/20 μs (Current)
Nominal Discharge Current (In) 5 kA (8/20 μs)
Max. Discharge Current (Imax) 10 kA (8/20 μs)
Protection Level (Up) < 25 V (at In = 5 kA, 8/20 μs)
General Data Number of Poles / Channels 2 (for series connection in one signal loop)
Connection Type Screw terminals
Mounting 35 mm DIN Rail
Housing Material Plastic
Operating Temperature -40 °C to +80 °C
Standards / Approvals IEC 61643-21, CE
Category Parameter Specification / Typical Value
Input Characteristics Input Voltage 100 - 240 VAC (Wide Range, Auto-Sensing)
Input Frequency 50 / 60 Hz
Input Current Max. ~1.5 A @ 100 VAC
Inrush Current Limiting Yes, NTC thermistor
Output Characteristics Output Voltage Approx. 14 V DC (Critical: Must verify actual value with datasheet)
Rated Output Current ~4.5 A (Calculated from 63W / 14V)
Rated Output Power 63 W
Efficiency Typically > 89% (Characteristic of high-end P3 series)
Ripple and Noise Typically < 100 mVpp
Line Regulation < 0.5%
Load Regulation < 0.5%
Monitoring & Signaling (HI11 Option) Signal Contact DC-OK Relay (Floating changeover contact)
Contact Rating Typically 24V DC / 2A (or 230V AC / 2A)
Function Changes state when output voltage is within normal range; indicates power failure.
Protection & Safety Overload Protection Electronic, auto-recovery
Overvoltage Protection Electronic, auto-recovery
Short-Circuit Protection Yes, electronic with auto-recovery
Standards CE, cULus Listed, GL (Marine)
Environmental & Mechanical Operating Temperature -25 °C to +70 °C (with derating above 60°C)
Cooling Method Fanless (Convection)
Mounting Standard 35 mm DIN Rail
Protection Rating IP20
Connections Screw Terminals
Category Parameter Specification / Typical Value
Input Characteristics Input Voltage 100 - 240 VAC (Wide Range, Auto-Sensing)
Input Frequency 50 / 60 Hz
Inrush Current Limiting Yes
Output Characteristics Output Voltage Likely 24 V DC (Must be verified with datasheet - other voltages like 12V or 48V are possible)
Rated Output Current ~2.6 A (if output is 24V)
Rated Output Power 63 W
Efficiency Typically > 89%
Ripple and Noise < 100 mVpp
Redundancy Function Redundancy Capability Yes, designed for parallel operation
Key Component Integrated OR-ing diode to prevent reverse current
Load Sharing Typically not active current sharing; relies on diode decoupling
Protection & Safety Overload Protection Electronic, auto-recovery
Overvoltage Protection Electronic, auto-recovery
Short-Circuit Protection Yes
Standards CE, cULus Listed
Environmental & Mechanical Operating Temperature -25 °C to +70 °C (with derating above 60°C)
Cooling Method Fanless (Convection)
Mounting Standard 35 mm DIN Rail
Connections Screw Terminals
Category Parameter Specification / Typical Value
Electrical Ratings Rated Voltage 300 VAC (3~ + PE)
Rated Current ~16 A (Critical: Must verify exact value with datasheet - common values are 16A, 20A, 30A for this form factor)
Frequency 50/60 Hz
Test Standards Safety Standards UL 60939, IEC 60939, EN 60939
EMC Standards Designed to meet CISPR 11/32, EN 55011/55032
Filter Performance Insertion Loss > 60 dB (Typical at 1 MHz)
> 40 dB (Typical at 100 kHz)
Leakage Current Line to Ground Typically < 5 mA (at 250VAC, 50Hz)
General Data Number of Phases 3-Phase + Protective Earth (PE)
Connection Type Screw Terminals (for both line and load sides)
Mounting Through-hole or bracket mounting (panel mount)
Operating Temperature -25 °C to +100 °C
Housing Material Metal case (typically aluminum) for shielding
Category Parameter Specification / Typical Value
Motor Protection Setting Current Range (Iᵣ) 0.06 - 0.6 A (This is the core protective range)
Tripping Class 10 (Standard) / 20 (e.g., for high-inertia loads) - Selectable
Protection Functions • Overload
• Phase Loss / Unbalance
• Jam Protection (with adjustable trip time)
• Earth Fault Protection (optional, depends on version)
Electrical Characteristics Rated Operational Voltage (Uᵢ) Up to 690 V AC
Supply Voltage (for electronics) Typically 24-240 V AC/DC (Auxiliary voltage for the relay's own circuitry)
Contacts Output Auxiliary Contacts • 1 NO (95-96) - Fault Signal
• 1 NC (97-98) - Fault Signal
Rated Current of Aux. Contacts Typically 6 A
General Data Mounting Snap-on to compatible Eaton contactors (e.g., DILM series)
Standards IEC/EN 60947-4-1, UL 508
Status Indication LED indicators for "Ready", "Alarm/Trip"
Ambient Temperature -20 °C to +60 °C
Category Parameter Specification / Typical Value
Application & Configuration Protected Circuit Signal circuits (e.g., 4-20 mA, digital I/O)
Circuit Configuration 2-pole (Line-to-Line and Line-to-Ground protection)
Connection In-series with the signal line
Electrical Characteristics Nominal Voltage 8 - 24 V DC (Typical for signal applications)
Max. Continuous Operating Voltage (Uc) ~30 V DC (Please verify in datasheet)
Nominal Current (In) Up to 250 mA (Suitable for most signal loops)
Voltage Drop < 1.5 V (Low, to minimize impact on the signal)
Surge Protection Performance Standards Complies with IEC 61643-21
Nominal Discharge Current (In) 5 kA (8/20 μs waveform)
Max. Discharge Current (Imax) 10 kA (8/20 μs waveform)
Protection Level (Up) < 40 V (at In, typical for this class)
General Data Mounting 35 mm DIN Rail
Connection Type Screw terminals
Housing Material Plastic (PA 6.6)
Operating Temperature -40 °C to +80 °C
Status Indication None (This is a basic model without visual fault indicator)