DVC6215
Technical Parameters
Category Parameter Specification / Description
General Model DVC6215
Description Digital Valve Controller (HART Protocol)
Product Family FIELDVUE
Input & Control Input Signal 4 to 20 mA DC, two-wire (sourcing)
Supply Pressure Minimum: 2.5 psig (0.17 bar) above actuator requirement
Maximum: See table below for supply pressure vs. enclosure material.
Characterization Linear, Quick-Open, Equal Percentage, and custom user-configurable
Performance Sensitivity 0.05% of span
Linearity ±0.5% of span (default)
Hysteresis Less than 0.2% of span
Air Consumption Steady State: ~0.04 SCFM (1.1 NLPM)
During Stroking: ~1.5 SCFM (42.5 NLPM)
Pneumatic Output Output Capacity Supply Relay: Up to 100 SCFM (2832 NLPM)
Exhaust Relay: Up to 40 SCFM (1133 NLPM)
Environmental Ambient Temperature Standard: -40°F to 185°F (-40°C to 85°C)
Extended: -40°F to 185°F (-40°C to 85°C) with specific seals.
Enclosure Rating Type 4X, 6 (IP66/67); Dust-tight and protected against water jets/immersion.
Material & Pressure Aluminum: Max 150 psig (10.3 bar)
Stainless Steel: Max 365 psig (25.2 bar)
Hazardous Area Certifications FM/CSA: Explosion-proof, Dust-ignition proof, Intrinsically Safe (Class I, II, III, Div. 1 & 2)
ATEX/IECEx: Ex db, Ex tb, Ex ia [ia] (Zone 1 & 21)
Physical Conduit Openings Two 1/2" NPT conduit openings
Pneumatic Connections Supply & Output: 1/4" NPT
Gauges: 1/8" NPT
Weight Aluminum: Approx. 4.5 kg (10 lbs)
Stainless Steel: Approx. 9.1 kg (20 lbs)